L5 COMMERCIAL FIRE ALARMS

L5 Classification:
  • A BS5839 L5 system will only have detectors where there is a very particular fire risk. It is not uncommon for there to only be one or two automatic detectors. 
  • Manual call points would be installed on all openings to fresh air and change of levels. 
  • Sounders would be installed throughout the building to achieve a minimum of 65dB of sound level (or 75dB at a bedhead if there is a sleeping risk). Sound would need to be 5dB above ambient noise up to a maximum of 120dB or flashing beacons would need to be fitted if this can not be achieved.
The Red areas show detection coverage
Typically used in:
  • Transportation terminals.
  • Prisons.
  • Buildings in which other fire precautions, such as means of escape, depart from recognised guidance.
  • Buildings with 'inner rooms', from which escape is possible only by passing through an 'access room', where there is inadequate vision between the 'inner room' and 'access room'.
  • Buildings in which automatic fire detection is required to operate other fire protection systems (e.g. magnetic door holders).
  • Situations in which fire could readily spread from an unoccupied area and prejudice means of escape from occupied areas.